To enter programming mode: PRESS FAN and MODE buttons at the same time. Then press the UP ARROW button while the fan and mode button are still held.

The clock display will change to indicate which programming mode you’re currently in.

The display will start at 10:00. If there is ever any inactivity for more than 20 seconds the thermo-stat will automatically return to normal operation.

Move digits up or down using up and down arrow buttons. Use HOLD button to move left one digit. Use MODE button to move right one digit. Also use the MODE button to select the values. Selected values are increased with the UP arrow button and decreased using the DOWN arrow button. MODE button will save current value and return to normal operation.

When finished programming tap the HOLD button until the thermostat is back in normal operation.

Screen Shot 2014-01-27 at 1.20.40 PM

 

11:11(Type)

01: Non Heat Pump (DEFAULT)

02: Heat Pump For changeover valve active on heat connect to terminal B. For

changeover value active on cool connect to terminal O.

11:21(Heat Type)

01: Electric (DEFAULT)

02: Gas/Oil When heating and the fan is on auto the fan operation is under the control of the HVAC unit and the fan relay is disabled.

12:11(Fan Speed) 

00: Reserved

01: Reserved

02: Reserved

03: Reserved

04: Single Speed with AUTO Fan Mode(DEFAULT)

12:21(System Mode) 

00: Cooling Only(COOL and OFF modes only)

01: Reserved

02: Heating Only(HEAT and OFF modes only)

03—05: Reserved

06: Manual Mode(COOL, HEAT, OFF) (DEFAULT)

07: Reserved

13:10(Calibration) 

-09 to 09: Temperature Calibration (DEFAULT = 00)

14:11(Differential) 

00-99: Differential 0.0 Degrees F to 9.9 Degrees F(DEFAULT = 05).

Defines the number of degrees in tenths the temperature must

move away from the setpoint before the unit turns on or off.

14:21(Occupancy Exit Delay) 

00-99: Exit Delay in Minutes (DEFAULT = 15)

14:31(Motion Only) 

00: Motion Only Enabled (DEFAULT)

01: Motion Only Disabled

15:11(Auto Mode Delay) 

00-99: Minimum Delay in minutes between mode changes (DEFAULT = 03)

15:21(Cool Mode Delay) 

00-99: Minimum Delay in minutes for change into Cool Mode (DEFAULT=2)

15:31(Heat Mode Delay) 

00-99: Minimum Delay in minutes for change into Heat Mode (DEFAULT=2)

16:11(Temperature Scale) 

00: Celsius

01: Fahrenheit (DEFAULT)

16:21(Minimum Cool Time) 

00-99: Minimum Time in Minutes Unit will run during a Cool Cycle (DEFAULT = 3)

16:31(Minimum Heat Time) 

00-99: Minimum Time in Minutes Unit will run during a Heat Cycle

(DEFAULT = 3)

16:41(Cool Maximum Runtime)

00-99: Maximum Continuous time in hours the unit will run during a Cool Cycle (DEFAULT = 00 (Disabled))

16:51(Heat Maximum Runtime) 

00-99: Maximum Continuous time in hours the unit will run during a Heat Cycle (DEFAULT = 00 (Disabled))

17:21(Display Type) 

00: Current Temperature Without Decimal Point

01: Current Temperature With Decimal Point

02: Setpoint Temperature Without Decimal Point

03: Setpoint Temperature With Decimal Point

18:11(Cool Setpoint Upper Limit) 

00-99: Upper limit of Cool Setpoint

18:21(Cool Setpoint Lower Limit) 

00-99: Lower limit of Cool Setpoint

18:31(Heat Setpoint Upper Limit) 

00-99: Upper limit of Heat Setpoint

18:41(Heat Setpoint Lower Limit) 

00-99: Lower limit of Heat Setpoint

21:10(Scan and Join Available HA Network) 

22:10(Reserved) 

23:10(Leave Network) 

24:10(Reserved) 

31:10(Set Clock Day) 

32:10(Set Clock Hours) 

33:10(Set Clock Minutes) 

41:00(Reset) 

42:00(Factory Reset) 

51:00(Reserved) 

52:00(Reserved)